Seaward 20A 3 Phase Insulation Adaptor
3 Phase Insulation Adaptor for use with PAT testers. This unit is for safety testing only.
SEA TPI-20A

Seaward 20A 3 Phase Insulation Adaptor
- Description
- More Information
Description
10A 3 Pin to 20A 5 Pin adaptor
Seaward 20 A 3‑Phase Insulation/Leakage Adaptor — Technical Specifications
Purpose:
This adaptor allows three‑phase appliances and equipment (up to 20 A or 32 A) to be tested for earth continuity and protective conductor leakage current using a compatible Seaward appliance tester. It enables tests under powered conditions on industrial machinery and 3‑phase appliances that cannot be tested with standard single‑phase leads.
General Description
-
Designed for use with compatible Seaward PAT testers (e.g., PAC3760DL, PAC3760 Plus, PAC3760 Plus II, Primetest Elite)
-
Provides connections for 3‑phase supply up to 20 A or 32 A with a 5‑pin (star) configuration
-
Enables earth continuity tests and protective conductor current measurements on 3‑phase equipment
-
Displays results (actual readings and Pass/Fail) on the Seaward tester’s screen
⚡ Technical Specification (Typical)
Rated Supply Voltage:
-
3‑phase mains supply (415 V nominal)
Current Rating:
-
20 A (primary adaptor rating; unit supplies 20 A capacity)
Connector Type:
-
5‑pin 3‑phase (STAR configuration) suitable for industrial connectors
Test Functions Supported (with Compatible Tester):
-
Earth Continuity Test – Checks protective conductor integrity under 3‑phase load
-
Leakage Current Measurement – Measures protective conductor leakage current while the equipment is energized
Display Range (Leakage Measurement):
-
Approximately 0.15 mA to 9.99 mA
Measurement Accuracy:
-
±(5% + 2 digits) typical for leakage measurement range
Pass Threshold (Leakage):
-
Approximately 5 mA (industry normative value for Class I protection)
Frequency Response:
-
50 Hz (standard mains frequency)
???? Operating Notes
-
Must be used only with a compatible Seaward tester that supports 3‑phase measurement
-
Powers up the 3‑phase appliance supply so internal circuits are active during testing
-
Insulation resistance tests on live 3‑phase loads may require dedicated insulation adapters and are not part of the standard leakage adaptor function
???? Typical Usage
-
Earth continuity and protective conductor current testing on 3‑phase industrial machinery, compressors, pumps, heavy-duty tools, and workshop equipment
-
Part of in-service electrical safety testing for industrial sites
???? Compatibility
-
Compatible with Seaward testers such as PAC3760DL, PAC3760 Plus, PAC3760 Plus II, Primetest Elite, and other units that support 3‑phase leakage test function