10A 3 Pin to 20A 5 Pin adaptor

Seaward 20 A 3‑Phase Insulation/Leakage Adaptor — Technical Specifications

Purpose:
This adaptor allows three‑phase appliances and equipment (up to 20 A or 32 A) to be tested for earth continuity and protective conductor leakage current using a compatible Seaward appliance tester. It enables tests under powered conditions on industrial machinery and 3‑phase appliances that cannot be tested with standard single‑phase leads.


General Description

  • Designed for use with compatible Seaward PAT testers (e.g., PAC3760DL, PAC3760 Plus, PAC3760 Plus II, Primetest Elite)

  • Provides connections for 3‑phase supply up to 20 A or 32 A with a 5‑pin (star) configuration

  • Enables earth continuity tests and protective conductor current measurements on 3‑phase equipment

  • Displays results (actual readings and Pass/Fail) on the Seaward tester’s screen


⚡ Technical Specification (Typical)

Rated Supply Voltage:

  • 3‑phase mains supply (415 V nominal)

Current Rating:

  • 20 A (primary adaptor rating; unit supplies 20 A capacity)

Connector Type:

  • 5‑pin 3‑phase (STAR configuration) suitable for industrial connectors

Test Functions Supported (with Compatible Tester):

  • Earth Continuity Test – Checks protective conductor integrity under 3‑phase load

  • Leakage Current Measurement – Measures protective conductor leakage current while the equipment is energized

Display Range (Leakage Measurement):

  • Approximately 0.15 mA to 9.99 mA

Measurement Accuracy:

  • ±(5% + 2 digits) typical for leakage measurement range

Pass Threshold (Leakage):

  • Approximately 5 mA (industry normative value for Class I protection)

Frequency Response:

  • 50 Hz (standard mains frequency)


???? Operating Notes

  • Must be used only with a compatible Seaward tester that supports 3‑phase measurement

  • Powers up the 3‑phase appliance supply so internal circuits are active during testing

  • Insulation resistance tests on live 3‑phase loads may require dedicated insulation adapters and are not part of the standard leakage adaptor function


???? Typical Usage

  • Earth continuity and protective conductor current testing on 3‑phase industrial machinery, compressors, pumps, heavy-duty tools, and workshop equipment

  • Part of in-service electrical safety testing for industrial sites


???? Compatibility

  • Compatible with Seaward testers such as PAC3760DL, PAC3760 Plus, PAC3760 Plus II, Primetest Elite, and other units that support 3‑phase leakage test function